Laserfiche WebLink
<br />e <br /> <br />e <br /> <br />BUILDINGS AND BUILDING REGULATIONS <br /> <br />~ 82-343 <br /> <br />Sec. 82-338. Aluminum conductors. <br /> <br />Aluminum conductors may not be used in any wmng within buildings, nor in any <br />underground service conductors. Aluminum conductors may only be used as outside aerial <br />conductors from a weatherhead to a pole, from a pole to a pole, and from a weatherhead to a <br />weatherhead. <br />(Ord. No. 1637, ~ 1(5.01), 3-13-89) <br /> <br />Sec. 82-339. Reserved. <br /> <br />ok <br /> <br />Editor's note-Section 1 ofOrd. No. 97-1637-B, adopted July 14,1997, repealed ~ 82-339 <br />in its entirety. Formerly, ~ 82-339 pertained to conduit in commercial buildings and derived <br />from ~ 1(5.02) of Ord. No. 1637, adopted March 13, 1989. <br /> <br /> <br />spaTe. <br /> <br />~ <br /> <br />(h) Ne" Iesidel.ce.!l of 1,969 or mOTe IHltlal'e feet Elf Ii-viRg apea, elfeltlaiag ettaekea ga:rages, <br />!lhall have seI vice elltrance capaei~ Elf not less thaR tRrce REl. 2 eElppel' aRa Bl'aReR eil'etlit <br />facilities ElfllOb less bRaR tell El-;el'eeTl'eRt ae.iees, t."El ofwRieR mest be left lift1'lsed as spal'ea. <br /> <br />(~ All underground services shall be installed in ~edule 40 conduit.l Q., M i h; M lA. M <br />(Ord. No. 1637, ~ 1(5.03), 3-13-89) <br /> <br />Sec. 82-341. Wil~a~ Ji-~~~i~8~el's aRd sllaee lteatel!s <br /> <br />Bra ch circuit wirl g for Wind~air condi . oning units~reSistanc~ype spa e heaters <br />shall no be smaller tha: no. 12 Jtl copper wir or its equiv lent and not ore tha one air <br />conditioni unit or air conditionin receptacle hall be in talled on one si Ie or <br />multiwire b nch circuit. <br /> <br /> <br />Sec. 82-342. Wiring within buildings. <br /> <br />Nonmetallic sheathed cable shall be used only for residential work~ apartment house:;;, <br />Conductors in or on all tile and masonry walls of such buildings shall be encased in rigid <br />conduit, flexible conduit, PVC conduit or electrical metallic tubing. Minimum size nonmetallic <br />sheathed cable shall be limited to No. 12 AWG. <br />(Ord. No. 1637, ~ 1(5.05), 3-13-89; Ord. No. 96-2079-E, ~ 3, 5-10-04) <br />RE-5.€RVE ~ . <br />Sec. 82-343. .GF8\1REI e8Rtaet. <br /> <br />EJlt"..t~~(;al Jn~tallk tl:1biI.g, iatermeaiate 1'I.etallic tliBiftg aRel BRest metall:leues sRall B9t 99 <br />liSta iR eElfttaet with the tariR. <br /> <br />(Old. No. 1631, ~ 1(5.86),13 13 89) - C) K <br /> <br />Supp. No. 10 <br /> <br />*' .;:::. ~M~-t.~ <br /> <br />CD82:19 <br /> <br />() I( <br /> <br />~ <br /> <br />~ <br />of <br /> <br />~ <br /> <br />