Laserfiche WebLink
<br />19fi}4 STANDARD FIRE CODE AMENDMENTS cont. <br /> <br />PAGE 15 OF 28 <br /> <br />(B) When a Class B assembly occupancy is located in a building above the <br />level of exit discharge, the entire building shall be equipped with a sprinkler system. <br /> <br />(C) When a Class C assembly occupancy is located in a building two (2) <br />stories or more above the level of exit discharget the entire building shall be .equipped <br />with a sprinkler system. <br /> <br />2. BUSINESS OCCUPANCIES <br /> <br />A business occupancy 3 stories or more in height shall be totally equipped with a <br />sprinkler system. <br /> <br />3. RESIDENTIAL OCCUPANCIES <br /> <br />(A) Hote/s, mote/st dormitories or lodging or rooming houses 3 stories or <br />more in height, with exterior means of egress, the entire bUilding shall be totally <br />equipped with a sprinkler system. <br /> <br />(B) Hotels, motels, dormitories or lodging or rooming houses 2 stories or <br />more in height, with interior means of egress, the entire building shall be totally <br />equipped with a sprinkler system. <br /> <br />(C) Apartment buildings, townhouses and condominiums 3 stories or:more in <br />height, with exterior means of egress, the entire building shall be totally equipped With <br />a sprinkler system. .r' :;,(" <br />' (D) Apartment buildings, townhouses and condominiums 2 stories or'rrl:Qrefin <br />height, with interior means of egress, the entire building shall be totally equipped'~ith a <br />sprinkler system. <br />(ORD. NO. 98-2222, ~ 2-9-98) <br /> <br />ADDED NEW SUBSECTION: <br /> <br />603.15.10 Flow and Tamper Switches <br /> <br />All buildings totally equipped with a sprinkler system shall have installed at each <br />riser, an approved electrically supervised waterflow and tamper switch. These switches <br />shall transmit an alarm to a fire alarm panel located in the building. The fire alarm <br />system, which has been installed as per NF/PA #72 specifications, shall transmit an <br />alarm (no automatic dialers) to the fire department dispatch office by way of a fire alarm <br />monitoring service or direct telephone line. <br />(ORD. NO. 98-2222, ~ 2-9-98) <br />