ORDINANCE NO. l388A
AN ORDINANCE AMENDING ORDINANCE 1388, AN ORDINANCE ADOPTING A FIRE
CODE FOR THE CITY OF LA PORTE; CONTAINING A SAVING AND REPEALING
CLAUSE; PROVIDING THAT ANY PERSON VIOLATING THE TERMS OF THIS
ORDINANCE SHALL BE FINED IN ANY SUM NOT MORE THAN TWO HUNDRED
DOLLARS ($200.00) AND EACH DAY OF VIOLATION SHALL BE DEEMED A
SEPARATE OFFENSE; AND PROVIDING AN EFFECTIVE DATE HEREOF.
BE IT ORDAI~rED BY THE CITY COUNCIL OF THE CITY OF LA PORTE:
Section 1. The 1983 edition of the Fire Code of the City of La
Porte, as adopted by Ordinance No. 1388, is hereby amended as set
forth on Exhibits nAn through nGn, both inclusive, attached hereto,
incorporated by reference herein, and made a part hereof, as fully
as if copied at length herein.
Section 2. Except as amended hereby, Ordinance No. 1388 shall
remain in full force and effect.
Section 3. Any person, as defined in Section 1.07(27), Texas
Penal Code, who shall violate any of the provisions of this code or
fails to comply with any order made hereunder, or who shall violate
any detailed statement of specifications or plans submitted and
approved hereunde:r, or any certificate of permit issued hereunder,
or who shall fail to comply with any lawful order of the fire
marshall or duly authorized representative within the time
specified, shall be guilty of a misdemeanor, and upon being found
guilty shall be punished by a fine of not more than Two Hundred
Dollars ($200.00). Each and every day a violation is permitted to
continue or compliance is not attained, or prohibited conditions are
maintained, shall constitute a separate and distinct offense. The
application of the above penalty shall not be held to prevent the
enforced removal of prohibited conditions.
Section 4. If any section, sentence, phrase, clause, or any
part of any section, sentence, phrase, or clause, of this ordinance
shall, for any reason, be held invalid, such invalidity shall not
affect the remaining portions of this Ordinance, and it is hereby
declared to be the intention of this City Council to have passed
each section, sentence, phrase or clause, or part thereof,
irrespective of the fact that any other section, sentence, phrase or
clause, or part thereof, may be invalid.
.
.
ORDINANCE NO. 1388A
Page 2
Section 5. This Ordinance shall be effective fourteen (14)
days after its passage and approval. The City Secretary shall give
notice of the passage of this Ordinance by causing the caption
hereof to be published in the official newspaper in the City of La
Porte at least twice within ten (IO) days after the passage of this
Ordinance.
Section 6.
The City Council officially finds, determines,
recites and declares that a sufficient written notice of the date,
hour, place and subject of this meeting of the City Council was
posted at a place convenient to the public at the City Hall of the
City for the time required by law preceding this meeting, as
required by the Open Meetings Law, Article 6252-17, Texas Revised
Civil Statutes Annotated; and that this meeting has been open to the
public as required by law at all times during which this ordinance
and the subject matter thereof has been discussed, considered and
formally acted upon. The City Council further ratifies, approves
and confirms such written notice and the contents and posting
thereof.
PASSED AND APPROVED, this 12th day of August, 1991.
F LA PORTE
BY
ATTEST: ~
~ ~~~~:r ~~
Cher ie- Black ~
City Secretary
APaz;z/~
Knox W. Askins
City Attorney
.
"A"
e
1. REOUESTED FIRE CODE CHANGES
ARTICLE 5- AIRPORTS. HELIPORTS AND HELISTOPS
DIVISION-4- AIRCRAFT SERVICE STATIONS, BULK FUEL STORAGE
AREAS AND LOADING DOCKS.
SECTION 5.17- INSTALLATION, OPERATION, MAINTENANCE OF
AIRCRAFT SERVICE STATIONS GENERALLY.
SUB-SECTION-3-
CHANGE FROM:: ABOVEGROUND FLAMMABLE OR COMBUSTIBLE
STORAGE TANKS OF ANY SIZE ARE PROHIBITED.
CHANGE TO:
ABOVEGROUND FLAMMABLE OR COMBUSTIBLE
STORAGE TANKS SHALL BE INSTALLED AS PER
N.F.P.A. #30 REQUIREMENTS, OR OTHER FIRE
CODE REVIEW COMMITTEE APPROVED STORAGE
SYSTEMS.
e
"8"
e
2. REOUESTED FIRE CODE CHANGES
ARTICLE-5- AIRPORTS. HELIPORTS AND HELISTOPS
DIVISION-4- AIRCRAFT SERVICE STATIONS, BULK FUEL STORAGE
AREAS AND LOADING DOCKS.
SECTION -5.18- BULK STORAGE AREAS AND LOADING RACKS.
SUB-SECTION -1-
CHANGE FROM: ABOVEGROUND FLAMMABLE AND COMBUSTIBLE
STORAGE TANKS OF ANY SIZE ARE PROHIBITED.
THE STORAGE OF COMBUSTIBLE LIQUIDS IN
ABOVEGROUND TANKS SHALL BE PROHIBITED IN
FIRE ZONES 1 & 3.
CHANGE TO: ABOVEGROUND FLAMMABLE AND COMBUSTIBLE
STORAGE TANKS SHALL BE INSTALLED AS PER
N.F.P.A. #30 REQUIREMENTS, OR OTHER FIRE
CODE REVIEW COMMITTEE APPROVED STORAGE
SYSTEMS.
.
"e"
.
3. REOUESTED FIRE CODE CHANGES
ARTICLE-16- FLAMMABLE AND COMBUSTIBLE LIOUIDS
DIVISION-2- ABOVEGROUND TANK STORAGE
SECTION-16.22- STORAGE IN ABOVEGROUND TANKS GENERALLY.
SUB-SECTION-A-
CHANGE FROM: THE STORAGE OF FLAMMABLE LIQUIDS IN
ABOVEGROUND TANKS IS PROHIBITED IN
THE CITY LIMITS OF LA PORTE.
CHANGE TO:
THE STORAGE OF FLAMMABLE LIQUIDS IN
ABOVEGROUND TANKS SHALL BE APPROVED
AND INSTALLED AS PER FIRE CODE
REVIEW COMMITTEE REQUIREMENTS.
e
"D"
e
4. REOUESTED FIRE CODE CHANGES
ARTICLE-16- FLAMMABLE AND COMBUSTIBLE LIQUIDS
DIVISION -2- ABOVEGROUND TANK STORAGE
SECTION-16.32- STORAGE IN ABOVEGROUND TANKS GENERALLY
SUB-SECTION-B-
CHANGE FROM:
CHANGE TO:
THE LOCATION AND INSTALLATION OF OUTSIDE
ABOVEGROUND TANKS, IN FIRE ZONE 2, WITH
RESPECT TO BUILDINGS AND PROPERTY LINES
FOR THE STORAGE OF COMBUSTIBLE LIQUIDS
SHALL BE IN ACCORDANCE WITH N.F.P.A.
PAMPHLET #30. THE FOLLOWING PROVISIONS
OF THIS SECTION SHALL APPLY EXCEPT WHERE
CONFLICTS EXISTS, THE MORE RESTRICTIVE
SHALL APPLY:
THE STORAGE OF COMBUSTIBLE LIQUIDS IN
ABOVEGROUND TANKS SHALL BE AS PER
N.F.P.A. #30 REQUIREMENTS, OR OTHER FIRE
CODE REVIEW COMMITTEE APPROVED STORAGE
SYSTEMS. THE FOLLOWING PROVISIONS OF THIS
SECTION SHALL APPLY EXCEPT WHERE CONFLICTS
EXISTS, THE MORE RESTRICTIVE SHALL APPLY:
.
"E"
e
5. REOUESTED FIRE CODE CHANGES
ARTICLE-16- F~~BLE AND COMBUSTIBLE LIOUIDS
DIVISION-5- BULK PLANTS
SECTION-16.26- PROHIBITED IN FIRE ZONE 1 AND 2
CHANGE FROM: NO BULK PLANT SHALL BE CONSTRUCTED WITHIN
THE LIMITS ESTABLISHED BY LAW AS FIRE ZONE
1 AND 2.
CHANGE TO:
NO BULK PLANT SHALL BE CONSTRUCTED WITHIN
THE CITY LIMITS OF LA PORTE, EXCEPT AS
PERMITTED BY THE FIRE CODE REVIEW COMMITTEE.
.
"F"
e
6. REOUESTED FIRE CODE CHANGES
ARTICLE-16- FLAMMABLE AND COMBUSTIBLE LIOUIDS
DIVISION-5- BULK PLANTS
SECTION-16.27- STORAGE OF FLAMMABLE OR COMBUSTIBLE LIQUIDS
SUB-SECTION-B-
CHANGE FROM:
CLASS 1- CLASS I FLAMMABLE LIQUIDS SHALL
BE STORED IN UNDERGROUND STORAGE TANKS
AS PER THIS ARTICLE.
CHANGE TO:
CLASS 1- CLASS I FLAMMABLE LIQUIDS SHALL
BE STORED IN N.F.P.A. #30 APPROVED
STORAGE TANKS, OR OTHER FIRE CODE REVIEW
COMMITTEE APPROVED STORAGE SYSTEMS.
.
"G"
e
7. REOUESTED FIRE CODE CHANGES
ARTICLE-16- FLAMMABLE AND COMBUSTIBLE LIOUIDS
DIVISION-12- REFINERIES, CHEMICAL PLANTS, DISTILLERIES
SECTION-16.81- STORAGE OF FLAMMABLE OR COMBUSTIBLE LIQUIDS
TO BE IN EITHER ABOVEGROUND OR UNDERGROUND
TANKS.
CHANGE FROM: FLAMMABLE LIQUIDS SHALL BE STORED IN TANKS
UNDERGROUND IN ACCORDANCE WITH DIVISION 3
OF THIS ARTICLE. COMBUSTIBLE LIQUIDS
SHALL BE STORED IN TANKS EITHER ABOVEGROUND
OR UNDERGROUND IN ACCORDANCE WITH
DIVISION 2 OR 3 OF THIS ARTICLE.
CHANGE TO: FLAMMABLE AND/OR COMBUSTIBLE LIQUIDS SHALL
BE STORED IN N.F.P.A. #30 APPROVED STORAGE
TANKS OR OTHER FIRE CODE REVIEW COMMITTEE
APPROVED STORAGE SYSTEMS.
1.. REQUESTED FIRE CODE CHAN.
ARTICLE 5- AIRPORTS. HELIPORTS AND HELISTOPS
DIVISION-~- AIRCRAFT SERVICE STATIONS, BULK FUEL STORAGE
AREAS AND LOADING DOCKS.
SECTION 5.17- INSTALLATION, OPERATION, MAINTENANCE OF
AIRCRAFT SERVICE STATIONS GENERALLY.
SUB-SECTION-3-
CHANGE FROM: ABOVEGROUND FLAMMABLE OR COMBUSTIBLE
STORAGE TANKS OF ANY SIZE ARE PROHIBITED.
CHANGE TO:
ABOVEGROUND FLAMMABLE OR COMBUSTIBLE
STORAGE TANKS SHALL BE INSTALLED AS PER
N.F.P.A. #30 REQUIREMENTS, OR OTHER FIRE
CODE REVIEW COMMITTEE APPROVED STORAGE
SYSTEMS.
Exhibit "A"
~. REQUESTED FIRE CODE C~
ARTICLE-5- AIRPORTS. HELIPORTS AND HELISTOPS
DIVISION-~- AIRCRAFT SERVICE STATIONS, BULK FUEL STORAGE
]~REAS AND LOADING DOCKS.
SECTION -5.18- BULK STORAGE AREAS AND LOADING RACKS.
SUB-SECTION -1-
CHANGE FROM: ABOVEGROUND FLAMMABLE AND COMBUSTIBLE
STORAGE TANKS OF ANY SIZE ARE PROHIBITED.
THE STORAGE OF COMBUSTIBLE LIQUIDS IN
ABOVEGROUND TANKS SHALL BE PROHIBITED IN
FIRE ZONES 1 & 3.
CHANGE TO: ABOVEGROUND FLAMMABLE AND COMBUSTIBLE
STORAGE TANKS SHALL BE INSTALLED AS PER
N.F.P.A. #30 REQUIREMENTS, OR OTHER FIRE
CODE REVIEW COMMITTEE APPROVED STORAGE
SYSTEMS.
Exhibit "B"
~3. REQUESTED FIRE CODE CH~
ARTICLE-16- FLAMMABLE AND COMBUSTIBLE LIQUIDS
DIVISION-2- ,~BOVEGROUND TANK STORAGE
SECTION-16.22- STORAGE IN ABOVEGROUND TANKS GENERALLY.
SUB-SECTION-A-
CHANGE FROM: THE STORAGE OF FLAMMABLE LIQUIDS IN
ABOVEGROUND TANKS IS PROHIBITED IN
THE CITY LIMITS OF LA PORTE.
CHANGE TO:
THE STORAGE OF FLAMMABLE LIQUIDS IN
ABOVEGROUND TANKS SHALL BE APPROVED
AND INSTALLED AS PER FIRE CODE
REVIEW COMMITTEE REQUIREMENTS.
Exhibi t "e"
.t,.. REQUESTED FIRE CODE CHp
ARTICLE-16- FLAMMABLE AND COMBUSTIBLE LIQUIDS
DIVISION -2- ABOVEGROUND TANK STORAGE
SECTION-16.32- STORAGE IN ABOVEGROUND TANKS GENERALLY
SUB-SECTION-B-
CHANGE FROM:
CHANGE TO:
THE LOCATION AND INSTALLATION OF OUTSIDE
ABOVEGROUND TANKS, IN FIRE ZONE 2. WITH
RESPECT TO BUILDINGS AND PROPERTY LINES
FOR THE STORAGE OF COMBUSTIBLE LIQUIDS
SHALL BE IN ACCORDANCE WITH N.F.P.A.
PAMPHLET #30. THE FOLLOWING PROVISIONS
OF THIS SECTION SHALL APPLY EXCEPT WHERE
CONFLICTS EXISTS, THE MORE RESTRICTIVE
SHALL APPLY:
THE STORAGE OF COMBUSTIBLE LIQUIDS IN
ABOVEGROUND TANKS SHALL BE AS PER
N.F.P.A. #30 REQUIREMENTS, OR OTHER FIRE
CODE REVIEW COMMITTEE APPROVED STORAGE
SYSTEMS. THE FOLLOWING PROVISIONS OF THIS
SECTION SHALL APPLY EXCEPT WHERE CONFLICTS
EXISTS, THE MORE RESTRICTIVE SHALL APPLY:
Exhibit "D"
, .
.. REQUESTED FIRE CODE CHp
ARTICLE-16- FLAMMABLE AND COMBUSTIBLE LIQUIDS
DIVISION-5- BULK PLANTS
SECTION-16.26- PROHIBITED IN FIRE ZONE 1 AND 2
CHANGE FROM: NO BULK PLANT SHALL BE CONSTRUCTED WITHIN
THE LIMITS ESTABLISHED BY LAW AS FIRE ZONE
1 AND 2.
CHANGE TO:
NO BULK PLANT SHALL BE CONSTRUCTED WITHIN
THE CITY LIMITS OF LA PORTE, EXCEPT AS
PERMITTED BY THE FIRE CODE REVIEW COMMITTEE.
Exhibit "E"
~6. REQUESTED FIRE CODE CH~ES
ARTICLE-16- FLAMMABLE AND COMBUSTIBLE LIQUIDS
DIVISION-5- BULK PLANTS
SECTION-16.27- STORAGE OF FLAMMABLE OR COMBUSTIBLE LIQUIDS
SUB-SECTION-B-
CHANGE FROM:
CLASS 1- CLASS I FLAMMABLE LIQUIDS SHALL
BE STORED IN UNDERGROUND STORAGE TANKS
AS PER THIS ARTICLE.
CHANGE TO:
CLASS I- CLASS I FLAMMABLE LIQUIDS SHALL
BE STORED IN N.F.P.A. #30 APPROVED
STORAGE TANKS, OR OTHER FIRE CODE REVIEW
COMMITTEE APPROVED STORAGE SYSTEMS.
Exhibit "F"
, .
e 7. REQUESTED FIRE CODE C~
ARTICLE-16- FLAMMABLE AND COMBUSTIBLE LIQUIDS
DIVISION-12- REFINERIES, CHEMICAL PLANTS, DISTILLERIES
SECTION-16.81- STORAGE OF FLAMMABLE OR COMBUSTIBLE LIQUIDS
TO BE IN EITHER ABOVEGROUND OR UNDERGROUND
TANKS.
CHANGE FROM: FLAMMABLE LIQUIDS SHALL BE STORED IN TANKS
UNDERGROUND IN ACCORDANCE WITH DIVISION 3
OF THIS ARTICLE. COMBUSTIBLE LIQUIDS
SHALL BE STORED IN TANKS EITHER ABOVEGROUND
OR UNDERGROUND IN ACCORDANCE WITH
DIVISION 2 OR 3 OF THIS ARTICLE.
CHANGE TO: FLAMMABLE AND/OR COMBUSTIBLE LIQUIDS SHALL
BE STORED IN N.F.P.A. #30 APPROVED STORAGE
TANKS OR OTHER FIRE CODE REVIEW COMMITTEE
APPROVED STORAGE SYSTEMS.
Exhibit "G"