<br />. <br /> <br />e <br /> <br />Table 3.4 <br />PROTECTION REQUIREMENTS AT <br />WATER LINE - FORCE MAIN CROSSINGS <br /> <br /> PROPOSED WATER <br />PRIMARY PROPOSED WATER PROPOSED FORCE MAIN <br />CONDITION EXISTING FORCE MAIN OR <br /> EXISTING WATER <br /> PROPOSED FORCE MAIN <br />SECONDARY WATER OVER WATER UNDER WATER OVER WATER UNDER <br />CONDITIONS FORCE MAIN FORCE MAIN FORCE MAIN FORCE MAIN <br /> Less Greater Less Greater Less Greater Less Greater <br />IF THE than 2' than 2' than 2' than 2' than 2' than 2' than 2' than 2' <br />CLEARANCE IS but less but less but less but less <br /> than 10' than 10' than 10' than 10' <br />*Protection 1 2 3 4a or 4b 5 6a 3 6a & 6b <br />Reauirement <br /> <br />J <br /> <br />*PROTECTION REOUlREMENTS FOR FORCE MAIN CROSSINGS <br />(All clearances shall be measured from outside wall to outside wall) <br /> <br />J. <br /> <br />Construct waterline with a 20-loot ductile iron section with all related appurtenances centered <br />above theforce main; 6-inch minimum clearance. <br />Construct water line with one 20footjoint ofC-90b, C-905 PVC centered above theforce main. <br />Not allowed. <br />a. Auger, bore &jack or microtunnell0feet minimum each side offorce main. Place one <br />10-loot joint of C-900 or C905. 150 psi, centered under sanitary sewer. Fill bore hole <br />with bentonite/clay mixture or grout; 2 foot minimum clearance. <br />b. OR replace the existingforce main with 150 psi lined ductile iron pipe with appropriate <br />adapters on all portions of the force main within J 0 feet of the water line. <br />Center a minimum 18 foot joint of force main, 150 psi lined ductile iron pipe under water line and <br />use cement-stabilized sand backfill for all portions of the sanitary sewer force main with 10 feet of <br />the water line as measured perpendicularly from any point on the water pipe to the sanitary sewer <br />force main pipe (minimum 2.5 sacks cement per cubic yard of sand). The cement-stabilized sand <br />bedding shall be from a point 6 inches below the bottom of the sanitary sewer force main to 6 <br />inches above the top of the sanitary sewer force main and one quarter of the pipe diameter of the <br />sanitary sewer force main on either side of the sanitary sewer force main. <br />Minimum 18 foot of sanitary sewer force main, 150 psi lined ductile iron pipe centered at the <br />water line. <br /> <br />2. <br />3. <br />4. <br /> <br />5. <br /> <br />6. <br /> <br />3.03 QUALITY ASSURANCE <br /> <br />A. Prepare calculations and drawings prepared under the supervision of a Texas Professional <br />Engineer trained and licensed under the disciplines required by the nature of the <br />drawings. The final design drawings, must be sealed, signed and dated by the <br />Professional Engineer responsible for development of the drawings. <br />B. For Elevated Stream and Ditch Crossings: .Prepare design calculations for support <br />columns and column spacing. <br /> <br />3.04 EXTRA TERRITORIAL JURISDICTION <br /> <br />The criteria herein described in this chapter shall be applicable to all water main and appurtenance <br />construction and all devices thereunto related within the ETJ of the City of La Porte except where <br />specifically denied or where specific exemptions for the ETJ have been enumerated. <br /> <br />January 2004 <br /> <br />Water System Design Criteria Page 13 of 13 <br />