Laserfiche WebLink
2018 IFC Update <br />2018 IFC Chapter 51: Aerosols <br />Code Section <br />Section Title Description of Change <br />2018 2015 <br />5103.2,5103.2, <br />Aerosol Products Limitations on aerosol products in plastic containers is revised and the use <br />5103.2.1,5103.2.1, <br />in Plastic of Plastic Aerosol X products is prohibited in higher life hazard occupancies. <br />5103.2.3,5103.2.3, <br />Containers <br />5104.1.2,5104.1.2, <br />5104.2.25104.2.2 <br />Modification <br />5104.8, <br />Aerosol Cooking Specific fire protection requirements are added to address aerosol cooking <br />5140.8.1, <br />Spray Products spray products. <br />5104.8.2, <br />5103.2.2, <br />5104.3.3, <br />5106.2.2 <br />Addition <br />2018 IFC Chapter 53: Compressed Gases <br />Code Section <br />Section Title Description of Change <br />2018 2015 <br />5306.1,5306.1, <br />Requirements for construction and ventilation of interior medical gas rooms <br />Medical Gas <br />5306.2,5306.2, <br />and gas cabinets are revised. <br />Storage <br />5306.2.1,5306.2.1, <br />5306.2.2,5306.2.2, <br />5306.2 5306.2 <br />Modification <br />5307.1,5307.1, <br />Requirements for liquefied CO2 in beverage dispensing applications have <br />Liquid Carbon <br />5307.3,5307.3, <br />been correlated with requirements for gas detection systems. <br />Dioxide Systems <br />5307.3.1,5307.3.1, <br />for Beverage <br />5307.3.2 5307.3.2 <br />Dispensing <br />Modification <br />5307.4, <br />Carbon Dioxide Carbon dioxide enrichment systems area regulated by the Fire Code when <br />5307.4.1, <br />Enrichmentthe system contains more than 100 pounds of CO2, or when the refill <br />5307.4.2, <br />Systems connection is remote from the tank or vessel. <br />5307.4.3, <br />5307.4.4, <br />5307.4.5, <br />5307.4.6, <br />5307.4.7 <br />Addition <br />2018 IFC Chapter 57: Mobile Fueling Operations <br />Code Section <br />Section Title Description of Change <br />2018 2015 <br />5707 <br />On-demand mobile fueling is allowed to occur at approved locations and <br />Mobile Fueling <br />Addition <br />under the control of a permit issued by the fire code official. <br />Operations <br />0 ¦¤ΐΒ <br /> <br />