Laserfiche WebLink
• 903.2.7.2 Group R-2. <br /> Add new subsection to read as follows: <br /> An automatic sprinkler system or a residential sprinkler system installed in accordance <br /> with section 903.3.1.2 shall be provided throughout all buildings with a group R-2 fire <br /> area that are more than two stories in height, including basement, or have more than <br /> sixteen dwelling units or sleeping units. <br /> 903.2.7.3 Group R-4. <br /> Add new subsection to read as follows: <br /> An automatic sprinkler system or a residential sprinkler system installed in accordance <br /> with Section 903.3.1.2 shall be provided throughout all buildings with a Group R-4 fire <br /> area. <br /> 907.1.1 Construction Documents. <br /> Amend by adding a new item to read as follows: <br /> • 12. System riser diagram <br /> 907.2.3 Group E. <br /> Amend this section by adding a second paragraph to read asfollows: <br /> Rooms used for sleeping or napping purposes within a day care use of Group E <br /> Occupancies must be provided with smoke detectors that comply with section <br /> 907.2.10.1.2. <br /> CHAPTER 11 AVIATION FACILITIES <br /> 1106.3 Construction of aircraft-fueling vehicles and accessories. <br /> Amend by adding an exception at the end of this section. <br /> Exception: A vehicle or trailer tank with a capacity of 250 gallons or less may be used for <br /> non-commercial refueling of private non-commercial aircraft if the following <br /> requirements are met: <br /> 1. The tank is placarded with no smoking signs, type of fuel contained in the tank <br /> • and the tank capacity; <br /> 2. The tank and all appurtenances used in the fueling operation are listed and <br /> approved for the specific purposes;and <br />