CHAPTER 9 FIRE PROTECTION SYSTEMS <br /> • <br /> 901.4 Installation of fire protection systems. <br /> Amend by adding an exception at the end of this section. <br /> Exception: Buildings temporarily closed due to seasonal operations may have their fire <br /> systems deactivated under the following conditions: <br /> 1. Building is unoccupied. <br /> 2. Building is properly secured. <br /> 3. All utilities are disconnected and drained. <br /> 4. The fire systems are certified as operational before the building is reoccupied. <br /> 5. A 24-hour a day fire.watch as defined in section 202 is provided during the <br /> interim between when utilities are reactivated and the fire systems are certified as <br /> operational. <br /> 6. The fire department must be notified of such closure. <br /> 7. A letter from the insurance carrier or,owner if self-insured, indicating knowledge <br /> of the closure is provided to the fire department. <br /> • 901.4.5 Marldng of Fire Protection Equipment. <br /> Amend by adding a new section to read as follows: <br /> Fire Department connection devices for building sprinkler systems in new and existing <br /> buildings shall be identified by the installation of approved reflective:markers or signs <br /> installed above the device in an unobstructed location at approximately 7 feet above <br /> grade. <br /> 901.9 Damage protection. <br /> Add a new subsection to read as follows: <br /> When exposed to probable vehicular damage due to proximity to alleys, driveways or <br /> parking areas, standpipes,post indicator valves and sprinkler system or standpipe system, <br /> connections shall be protected in an approved manner. <br />