<br />-----Original Message----- <br />From: Huber, Mark [mailto:HuberM@ci.la-porte.tx.us] <br />Sent: Friday, February 20, 2004 3:02 PM <br />To: 'melissa@thesligroup.com' <br />Cc: Christensen, Laurie; Wilmore, Debbie; Huber, Mark <br />Subject: RE: 9601 Fairmont 1st United Meth. Church <br /> <br />Melissa, <br /> <br />Thank you for bringing Section 503.4.4 to my attention. If all the conditions of that section can be <br />met\achieved, then we agree. no fire sprinkler would be required up to 12,000 sq.ft max limit. <br />However, the four hour fire wall is still required separating proposed from existing. My review of <br />this issue with the fire marshal resulted with her strongly recommending (but not required) that <br />you install a fire sprinkler and or monitored alarm system. <br /> <br />Mark Huber <br /> <br />-----Original Message----- <br />From: Melissa Centanni [mailto:melissa@thesligroup.com] <br />Sent: Thursday, February 12, 2004 3: 11 PM <br />To: 'Huber, Markt <br />Subject: RE: 9601 Fairmont 1st United Meth. Church <br /> <br />Mark, <br /> <br />We found the same information as stated below with one change. Table 500 for A-2 <br />Small Assembly Type IV Unprotected construction provides for 8,000 sq. ft. then section <br />503.4.4 provides for an area increase of 50%. This brings the total allowable area up to <br />12,000 sq. ft. without a fire sprinkler system. <br /> <br />Please let me know if this is acceptable. <br /> <br />Thank you, <br /> <br />Melissa Centanni <br /> <br />The S.LI. Group, Inc <br /> <br />713-465-4650 x123 <br /> <br />-----Original Message----- <br />From: Huber, Mark (mailto:HuberM@ci.la-porte.tx.us] <br />